Select your PLC brand to identify your protocol and MOFF support status.
S7-1200 and S7-1500 support native OPC-UA, fully supported by MOFF today. Older S7-300/400 is read directly over S7comm, supported today. PROFINET-only setups: bridge via OPC-UA.
OPC-UA: NOWS7comm: NOWControlLogix and CompactLogix are read directly over EtherNet/IP (CIP), supported today. No gateway needed.
EtherNet/IP: NOWModicon M340/M580 supports both Modbus TCP and OPC-UA natively. Both fully supported by MOFF today.
OPC-UA: NOWModbus TCP: NOWTwinCAT 3 has excellent native OPC-UA support, fully supported today.
OPC-UA: NOWNX/NJ series supports OPC-UA natively. FINS over Ethernet is on the roadmap.
OPC-UA: NOWFINS: RoadmapAC500 PLC supports both Modbus TCP and OPC-UA. Both fully supported today.
OPC-UA: NOWModbus TCP: NOWOlder Danfoss drives use Modbus RTU or PROFIBUS. Modbus RTU/TCP is fully supported.
Modbus RTU/TCP: NOWPROFIBUS: RoadmapSCADA-RTU telemetry over IEC 60870-5-104 is supported today. IEC 61850 and DNP3 are on the roadmap; bridge those via OPC-UA gateway for now.
IEC 60870-5-104: NOWIEC 61850 / DNP3: RoadmapBuilding systems are read directly over BACnet/IP, supported today.
BACnet/IP: NOWMost controllers built after 2015 support OPC-UA or Modbus TCP. Both fully supported today. Book a demo and we identify your stack together.
OPC-UA + Modbus TCP: NOWDenmark’s NIS2 Act (Act no. 434 of 6 May 2025) took effect on 1 July 2025. Energy, including district heating, is covered by a separate act in force since 7 March 2025. Here is what it means for your plant.
This is a summary, not legal advice.
Who changed that setpoint at 03:17? Every reading is signed and chained before it leaves the floor, so the answer exists before anyone asks.
Read-only. Never writes to your OT network. If a destination goes down, MOFF buffers locally and delivers automatically when it reconnects. ZERO LOSS.
Every value an agent reads is signed and chained, so its answer can be traced back to the reading it came from.
And if anyone changes the data afterwards, the agent would know. A changed value no longer matches its signature, and the chain says so on the next verification.
It runs locally with zero data egress, or with a cloud provider you choose.
The layer is in use today for tag mapping. Analysis of what changed is on the roadmap.
Many plants still move data by hand between OT and IT, and the record of what happened is assembled only when an audit, an incident or an authority asks for it.
MOFF builds a continuous, verifiable record from PLC to IT system, so the evidence already exists when it is needed.
Why organisations are looking at this now →The technical argument is the easy half. These are the four lines that decide whether a plant manager, a CFO or a compliance owner signs.
Six protocols read live today. Every value signed at capture and chained. Six delivery paths out, trend history inside, and a one-click evidence bundle your auditor can verify without us.
See the platform →NIS2 asks operators of essential services to manage risk, document their measures, and report incidents on a deadline. Here is what MOFF gives you for that.
30 minutes on your protocols. Collected, signed, verified while you watch. No slides, no sales theatre.
Or answer six questions first and see the fit yourself: Plant Fit →